DB2016
ARITECH 2000 Series base with isolator
- Protection against overload conditions
- Automatic restore when fault is corrected
- LED indicates isolation condition
- Detector connected to isolator remains operational
Related products
At a glance
General
The DB2016 isolator base senses and isolates overload and short circuit faults on a 2000 series fire detector loop. A yellow LED on the device indicates an isolation condition. The detector connected to the DB2016 still receives power in the event of a single short circuit. If every detector in the loop is fitted with an isolator base, no devices are lost in the event of a single short circuit.
Functionality and use
The function of the DB2016 is to protect the integrity of the addressable loop in the case of an overload or short-circuit on part of the loop. In such event, the entire data circuit is not lost but only the effected part of the loop is isolated.
For full protection it is recommended that every detector be fitted with a DB2016 isolator base. For regulatory purposes it is specified that not more than a single detection zone is affected by a single fault on the loop, containing no more than 32 devices.
The DB2016 is only suitable for use in dry areas.
For full protection it is recommended that every detector be fitted with a DB2016 isolator base. For regulatory purposes it is specified that not more than a single detection zone is affected by a single fault on the loop, containing no more than 32 devices.
The DB2016 is only suitable for use in dry areas.
Details
- Protection against overload conditions
- Automatic restore when fault is corrected
- LED indicates isolation condition
- Detector connected to isolator remains operational
Technical specifications
| General | ||
|---|---|---|
| Status indication |
Yellow LED
|
|
| Compatibility |
Aritech 2000 series point detectors
|
|
| Connectivity |
2-wire loop, earth & remote indicator
|
|
| Addressing method |
No addressing required
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
Loop powered
|
|
| Operating voltage |
17 to 34 V (28 V nominal)
|
|
| Current consumption |
30 µA (standby)
<1.6 mA (isolated)
|
|
| No. of cable cores |
2
|
|
| Terminals |
5
|
|
| Detection | ||
|---|---|---|
| Monitoring |
Short circuit
|
|
| Isolation | ||
|---|---|---|
| Type |
Negative line break
|
|
| Isolation voltage |
14 V
|
|
| Reconnect voltage |
14.5 V
|
|
| Switch current |
800 mA (max)
|
|
| Series resistance |
0.1 Ω
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
101 x 13.5 mm (Ø x H)
|
|
| Net weight |
49 g
|
|
| Colour |
Cloud white (RAL 9001)
|
|
| Mounting type |
Ceiling mount
|
|
| Cable entries |
1
|
|
| Material (body) |
Plastic
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-10 to +50°C
|
|
| Storage temperature |
−10 to +70ºC
|
|
| Relative humidity |
10 to 95% noncondensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP30
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RoHS 2
WEEE
|
|
| Certification |
CPR
|
|
| Standards |
EN54-17
|
|
Downloads
All downloadsDatasheet
Certificates
DoP
KGS F&S - DoP_360-4227-0699_DB2016
Non EU certificate
VMC_AEAI - VKF_22294 - 24819_2X Aritech
DoC
DoC_10-4227-356-0299_DP2061T
DoC
KGS F&S - DoC_10-4229-356-0099_DT2063N
Installation sheet
CPD / CPR
CPD / CPR
CPR_1134-CPR-023_DP2061T
CPD / CPR
CPR_0786-CPR-20635_DB2016
CPD / CPR
CPR_0370-CPR-2410_DT2063N
CPD / CPR
CPR_1134-CPR-010_DP2061N
Other EU certificate
Other EU certificate
VMC_ANPI_B-9212-FD-865-e_FP1216C
Other EU certificate
VMC_ANPI_B-9212-FD-863e_FP1216C-xx
Other EU certificate
VMC_B-9212-FD-1088-b_2X-A series
Other EU certificate
VMC_232.295_2X-A, 2X-AT
Other EU certificate
VMC_PR-2015/064_2X-A Series
Other EU certificate
VMC_PR-1719/064_2X
Other EU certificate
VMC_APF-1360_2X
Technical documentation
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.