The 2010-2-PIB-8I Peripherals Interface Board is an accessory of the small to medium size intelligent addressable life safety control systems. In total there are 4 variants of this board. The 2010-2-PIB-8I is a reduced variant of the 2010-2-PIB and is perfect if your only looking for having additional supervised inputs to interface other electronic equipment on site.

Functionality

The 2010-2-PIB-8I Peripherals Interface Board provides eight inputs for compatible control panels. Inputs and outputs are supervised for short circuit and open circuit faults.

Mounting & connections

The board can be plugged directly on the front of the main board inside the big size control panel variants on top of the new release 3 chassis. No additional wiring is required. You can use the pluggable connectors to make your connections to the field wiring. Connect an external power supply to the board directly to reduce the load of your system.

Details

  • 8 supervised inputs
  • Pluggable connectors

Technical specifications

General
Compatibility
Release 3 hardware / firmware
Electrical
Power supply type
VDC
Operating voltage
24 VDC
Current consumption
40 mA max. (standby)
Input
Termination
EOL 15 kOhm, 1/4 W resistor
Physical
Form factor
Large
Physical dimensions
105 x 192 mm (W x H)
Net weight
105 g
Shipping weight
240 g
Mounting type
In cabinet
Environmental
Operating temperature
+5 to +40°C
Storage temperature
-20 to +50°C
Relative humidity
10 to 95% noncondensing
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR
Standards
EN54-2, EN54-13
Input activation
Open circuit >20.2 kOhm
Quiescent 15 kOhm
Activated 60.2 Ohm to 8 kOhm
Short circuit <60.2 Ohm

Downloads

All downloads

Datasheet

Installation sheet

Certificates

Other EU certificate