FF-AP1N
Air Purge for FF7x series
Na pierwszy rzut oka
Application
The Air Purge kit is intended to be mounted in between a Flame Detector (FF7x series - Non Exd versions) and adjustable mounting bracket (FF705), with the Air Purge kit nozzle positioned to channel air from the inlet onto the window of the flame detector to prevent obscuration by particles.
Successor of FF-AP1
Mounting
The Air Purge nozzle must be angled at 30° from horizontal in order to maximize the air flow over the front window.
Installation
The purge air adapter should be connected to an external air supply via the female 1/4” BSP non return valve.
The air should be oil free and dry with a pressure range from 7psi (0.5Bar) to 50psi (3.5Bar).
If the air is not required continuously to keep the viewing window clean then a pulse of air can be supplied at regular intervals.
Caution: This product is not suitable for use in ATEX zone 0 - For use in ATEX zone 1/21 or 2/222, air must be clean and the system blown through before placing in a hazardous environment
The air should be oil free and dry with a pressure range from 7psi (0.5Bar) to 50psi (3.5Bar).
If the air is not required continuously to keep the viewing window clean then a pulse of air can be supplied at regular intervals.
Caution: This product is not suitable for use in ATEX zone 0 - For use in ATEX zone 1/21 or 2/222, air must be clean and the system blown through before placing in a hazardous environment
Specyfikacja techniczna
| Physical | ||
|---|---|---|
| Mounting type |
Screw / bolt mount
|
|
Pobrania
All downloadsKarta katalogowa
Jeśli są dostępne, pliki do pobrania Certyfikatów, oprogramowania i oprogramowania sprzętowego oraz nośników są wyświetlane w ich języku domyślnym.